Answer: (1) Fault phenomenon. The compressed air system contains a large amount of water, and the drain valve continuously releases a large amount of water.
(2) Cause analysis.
1) The cooler leaks;
2) The cold dryer or dryer does not work properly;
3) The air tank is not drained regularly.
(3) Elimination method.
1) Eliminate the leak or replace the cooler after leak detection;
2) Eliminate the fault of the cold dryer or dryer;
3) Drain the air compressor tank regularly.