Answer: (1) Since the screw air compressor itself has very little vibration, the air compressor only needs to be installed on a hard, flat and horizontal ground. If a rubber vibration damping pad or wooden board with a thickness of 8~15mm is added, it will be more beneficial to vibration and noise reduction.
(2) Take the processing surface or base plane parallel to the ground plane on the machine as the reference, and use a spirit level to measure the horizontal level. It is better to control the vertical and horizontal levels within the range of 2mm/m.
(3) The cooling water used for water-cooled air compressors should meet the industrial water standards. When using a cooling water tower circulation system, softeners should be added regularly to keep the circulating water clean.
(4) The cooling water pressure is generally maintained between 0.15~0.25MPa, and the maximum does not exceed 0.5MPa.
(5) The cooling water outlet temperature should be lower than 40℃.
(6) If it is an air-cooled air compressor, in addition to meeting the above environmental requirements, the heat exchanger should be cleaned frequently to maintain efficient heat exchange.